Product Introduction

SLIQUID GLOBAL Coolant Distribution Unit (CDU) is a liquid cooling heat exchange equipment product launched to address the cooling issues of ultra-high-density cold plate liquid-cooled servers. The CDU is designed to meet the cooling needs of cold plate liquid-cooled IT equipment and is the core equipment of the cold plate liquid cooling system. It is mainly used for the circulation and cooling of the coolant in the liquid cooling system, while also achieving heat exchange between the outdoor side cooling water and the secondary side coolant, as well as cold energy management and distribution.

Product Advantages

Diverse Product Specifications
Platform-based design, with a variety of heat exchange capacities (10-1200kW) available, providing adaptation for various load requirements.
High Adaptability
Includes two forms: rack-mounted and cabinet-style, with both air-cooled and water-cooled cooling methods, perfectly adapted to a variety of computer room scenarios.
Multiple Control Modes
Offers a variety of operating modes to choose from, Such as constant pressure, constant flow, and constant temperature liquid supply etc.
Fully Automated Control Functions
Equipped with detection functions for temperature, pressure, flow rate, conductivity, leakage, and dew point, supporting functions such as anti-condensation, parallel machine group control, and remote configuration etc.
Precise Control Accuracy
The steady-state control accuracy of the outlet liquid temperature can reach ±0.5°C, and the dynamic control accuracy can reach ±3°C, Flow rate infinitely adjustable from 0 to 100%
More Reliable and Safe
Key components are designed with redundancy, enhancing the system's reliability. The heat exchange capacity is designed with redundancy, allowing for a maximum of 10% excess heat exchange capacity; built-in check valves are included to prevent reverse flow in parallel operation.
Easy to Operate and Maintain
Supports online maintenance of key components, with a built-in coolant storage device, supporting online automatic coolant replenishment, making operation and maintenance convenient.

CDU-0010W

CDU-2030W

CDU-2055W

Technical Specification

Types CDU-0010W CDU-2030W CDU-2055W CDU-2300W CDU-2600W CDU-21200W
Installation Type Rack-Mounted Rack-Mounted Rack-Mounted Cabinet-Style Cabinet-Style Cabinet-Style
Heat Exchange Form Air-Liquid Liquid-Liquid Liquid-Liquid Liquid-Liquid Liquid-Liquid Liquid-Liquid
Rated Cooling Capacity 10kW 30kW 55kW 320kW 500kW 1200kW
Secondary Side Rated Flow Rate(m³/h) 0.9 2.7 5.0 28 46 108
Primary side pressure drop/(kPa) / ≤100 ≤100 ≤100 ≤100 ≤100
Dimensions 8U 4U 6U 600*1200*2000 900*1200*2200 1200*1400*2200
Primary Side Interface Specifications / Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 50.5mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 50.5mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 91mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 119mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 155mm
Secondary Side Interface Specifications Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 50.5mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 50.5mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 50.5mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 91mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 119mm Hygienic Stainless Steel Quick-Connect Chuck with an Outer Diameter of 155mm
Rated Output Pressure Differential (Customizable to Increase Output Pressure Differential) 100kPa 100kPa 100kPa 120kPa 120kPa 120kPa
Rated Operating Condition 25℃ Inlet Air Temperature Primary side supply/return liquid temperature 35/45°C, Secondary side supply/return liquid temperature 40/50°C, Secondary side calculated based on 20% ethylene glycol.

CDU-2300W

CDU-2600W

CDU-21200W