Product Introduction
Chilled water in-row air conditioners are an end form of the chilled water system, using a horizontal air delivery method. The air conditioner is installed close to the heat source, side by side with the cabinets, and in conjunction with cold and hot aisle containment technology, effectively addresses the high-density heat dissipation issues in the data center.
Scheme Features
- Energy-saving Configuration
- The humidification method uses a wet film humidifier, which saves more than 95% energy compared to electrode humidification. It has a group control function that can meet the group control of 32 units, avoiding overlapping cooling and achieving significant energy savings.
- High Adaptability
- Equipped with EC centrifugal fans, it has a high static pressure of the outgoing wind, which can adapt to long-distance air delivery environments. An optional strong drainage component is available to meet on-site drainage requirements.
- User-friendly Interface
- It features a 7-inch color touch control screen that displays key parameters such as temperature and humidity in real time, making operation simple. The self-diagnostic intelligent information processing accurately outputs fault information, guiding operational and maintenance personnel in maintenance.
Technical Specification Sheet
Types | Name/Unit | CIS-70C |
---|---|---|
Performance Parameters | Total Cooling Capacity(kW) | 75 |
Sensible Heat Ratio | ≥95% | |
Water Flow Rate(m³/h) | 12.8 | |
Water Side Pressure Drop(kPa) | ≤100 | |
Pressure Resistance(Mpa) | 1.6 | |
Airflow(m³/h) | 11500 | |
Numbe of Fans(PCS) | 3 | |
Heating Capacity(kW) | 6 | |
Humidifying Capacity(kg/h) | 3 | |
Pipe Connection Specifications | Inlet and Outlet Water Pipe Connection Sizes | DN40 |
Inlet and Outlet Pipe Connection ways | Thread G 1-1/2″ | |
Humidity Humidifier Inlet Interface | OD10(Tower Type Connector) | |
Drain Pipe Diameter(mm) | ID16╳OD24 | |
Electrical Parameters | Power Supply Specifications | 380VAC/3ph/50HZ |
Max Current¹ (A) | 13.5 | |
Recommended Power Cord Specifications(mm2) | 5×2.5 | |
Recommended Circuit Breaker Specifications for Indoor Units(A) | 16 | |
Dimensions Width×Height×Depth |
Solid Door+LED Design | 600mm×2000mm×1365mm |
Solid Door+LED Design | 600mm×2000mm×1565mm | |
Mesh Door+LED Design | 600mm×2000mm×1265mm | |
Mesh Door+LED Design | 600mm×2000mm×1365mm | |
Mesh Door | 600mm×2000mm×1200mm | |
Weight (kg) | 298 |
*Note:
1. ①These parameters are for the configuration under constant temperature and humidity conditions;
2. Operating conditions: Indoor at 37℃/24%RH, outdoor at 35℃. If you have any other requirements, please contact our company.