Product Introduction
In-row air conditioning, also known as row-based air conditioning, is a high-efficiency, energy-saving data center precision air conditioning product. Installed side by side with the racks, these air conditioners use a horizontal airflow pattern with front air supply and rear air return, effectively addressing issues of air mixing and short-circuiting in the data center. With an ultra-high sensible heat ratio and minimal heat loss, combined with cold and hot aisle containment technology, they can precisely control the temperature and humidity in the data center.
Main Function
- High-efficiency Cooling
- Close to the heat source, horizontal air delivery, using a high air supply and return design, the cooling efficiency is higher.
- Precise Temperature Control
- Equipped with a high-efficiency DC inverter compressor, EC (Electronically Commutated) fans, and an electronic expansion valve to achieve rapid response to cooling demands and seamless adjustment of cooling capacity.
- Premium Design
- Choose a high-grade, sophisticated appearance that integrates modern technological elements, complements the overall style of the data center, and meets personalized needs.
- Energy-saving Configuration
- Optional energy-saving module, intelligently switches working modes according to ambient temperature, maximizes the use of natural cold sources, and achieves a comprehensive PUE of less than 1.2 (in Beijing).
Application Scenarios
Matches with single-row, double-row, and pool-level micro-module integrated solutions.
- 01
- Row-level application, in conjunction with enclosed network cabinets, forms independent cold and hot aisles at the front and back. The air conditioner delivers cold air to the front of the equipment cabinets, which is then used by the IT equipment. After cooling the IT equipment, the warm air is returned from the back of the air conditioner.
- 02
- Pool-level application, utilizing aisle containment technology to create cold and hot aisles, the air conditioner delivers cold air into the cold aisle, which is then utilized by the IT equipment. After the IT equipment is cooled, the warm air is returned through the back of the air conditioner.
- Premium Design
- Choose a high-grade, sophisticated appearance that integrates modern technological elements, complements the overall style of the data center, and meets personalized needs.
- Energy-saving Configuration
- Optional energy-saving module, intelligently switches working modes according to ambient temperature, maximizes the use of natural cold sources, and achieves a comprehensive PUE of less than 1.2 (in Beijing).
Technical Specification Sheet
Indoor Unit | Name/Unit | CIE-25A | CIE-40A | CIE-50A | CIE-60A |
---|---|---|---|---|---|
Performance Parameters | Total Cooling Capacity(kW) | 25 | 40 | 50 | 60 |
Sensible Heat Ratio | ≥95% | ≥95% | ≥95% | ≥95% | |
Airflow(m³/h) | 5000 | 8500 | 10800 | 12000 | |
Number of Fans(PCS) | 6 | 4 | 3 | 3 | |
Heating Capacity(kW) | 3 | 6 | 9 | 9 | |
Humidifying Capacity(kg/h) | 3 | 3 | 4.5 | 4.5 | |
Electrical Parameters | Power Supply Specifications(—) | 380VAC/3ph/50HZ | 380VAC/3ph/50HZ | 380VAC/3ph/50HZ | 380VAC/3ph/50HZ |
Max Current¹ (A) | 23.4 | 41.6 | 48 | 52 | |
Recommended Power Cable Specifications(mm2) |
5×6.0 | 5×10 | 5×16 | 5×16 | |
Recommended Circuit Breaker Specifications for IndAirflowoor Unit(A) |
32 | 63 | 63 | 63 | |
Pipe Connection Specifications | Refrigerant Gas Pipe Specifications(mm) | 16 | 19 | 22 | 22 |
Refrigerant Liquid Pipe Specifications(mm) | 12 | 16 | 16 | 16 | |
Physical Dimensions | Width(mm) | 300 | 600 | 600 | 600 |
Depth(mm) | 1100/1200 | 1100/1200 | 1100/1200 | 1100/1200 | |
Height(mm) | 2000 | 2000 | 2000 | 2000 | |
Weight(kg) | 235 | 235 | 310 | 310 |
Outdoor Unit | Name/Unit | COE-38F | COE-54F | COE-88F | COE-88F |
---|---|---|---|---|---|
Dimensions | Width(mm) | 1610 | 1020 | 1100 | 1100 |
Depth(mm) | 653 | 1200 | 1275 | 1275 | |
Height(mm) | 982 | 1840 | 1985 | 1985 | |
Weight(kg) | 130 | 150 | 240 | 240 | |
Electrical Parameters | Recommended Power Cable Specifications(mm2) | 5×1.5 | 5×1.5 | 5×1.5 | 5×1.5 |
Signal Cable(mm2) | 2×0.5 | 2×0.5 | 2×1.0 | 2×1.0 | |
Recommended Circuit Breaker Specifications for Outdoor Unit(A) | 10 | 10 | 10 | 10 |
*Note:
1. ①These parameters are for the configuration under constant temperature and humidity conditions;
2. Operating conditions: Indoor at 37℃/24%RH, outdoor at 35℃. If you have any other requirements, please contact our company.