Product Introduction
The liquid-cooled water-saving outdoor unit is a product specifically designed for heat dissipation in liquid-cooled data centers. It features high reliability, large airflow, efficient heat exchange, and ultra-low water consumption. Its corrosion resistance and water-saving characteristics make it well-suited for the construction needs of high-density computer rooms in areas with water scarcity or limited water resources. It provides cooling water that is compatible with liquid cooling temperature control systems or other projects that require cooling water.
Product Advantages
- Energy-saving and Water-saving
- Utilizing centrifugal micro-mist spraying technology, there is no need for a separate configuration of a booster pump. The mist produced is parallel, with smaller droplets, resulting in better evaporative cooling effects.
- The spraying system is not required for most of the operating time, effectively reducing the use and waste of water resources.
- Low Maintenance Cost
- The structure is simple, with a low failure rate, reducing the workload and cost of maintenance and repair.
- In winter, there is no need for spraying, which avoids the issue of water freezing in the spray system. The cooling system has a simple structure, reducing the complexity of maintenance and operation.
- Highly Efficient and Reliable
- It can achieve continuous operation for 365 days × 24 hours;
- Equipped with high-efficiency EC fans, it achieves stepless adjustment and starts without electrical current impact.
- A powerful intelligent control system, utilizing PID regulation technology, also features comprehensive alarm protection and expert-level self-diagnostic capabilities.
Technical Specification Sheet
Types | Name/Unit | FCM-600W |
---|---|---|
Performance Parameters | Heat Exchange Capacity(kW) | 600 |
Fan Specifications | Air Volume(m³/h) | 200000 |
Number of Fans (PCS) | 8 | |
Fan Type | EC Fan | |
Coolant Parameters | Coolant | Water or Glycol Solution |
Inlet and Outlet Water Temperature(℃) | 45/35Customizable with a 5-10°C temperature difference for inlet and outlet water | |
Water Flow Rate (m³/h) | 56 | |
Water Side Pressure Drop(kPa) | ≤70 | |
Fitting Specifications | Inlet Pipe Specifications(mm) | DN100╳2 |
Outlet Pipe Specifications(mm) | DN100╳2 | |
Inlet and Outlet Pipe Connection Type | Flange Connection | |
Electrical Parameters | Power(kW) | 16 |
Power Supply | 380VAC/3ph/50HZ | |
Fitting Specifications | (Length×weigh×Height)(mm) | 6000╳2300╳2850 |
Weight(kg) | 1900 |
*Note:
Operating conditions: Indoor at 37℃/24%RH, outdoor at 35℃. If you have any other requirements, please contact our company.